Fire Alarm Systems | FPA‑1000‑UL Analog Addressable Fire Panel
The FPA‑1000‑UL Analog Addressable Fire Panel is an
advanced analog control panel for small to medium
facilities in commercial or public building applications.
The FPA‑1000‑UL combines complete built-in Fire Alarm
Control Panel (FACP) equipment such as Notification
Appliance Circuits (NACs), Signaling Line Circuits (SLCs),
relays, power supply, Digital Alarm Communicator
Transmitter (DACT), and Ethernet connection with
expandability using the option bus or plug‑in boards. The
two integrated NACs can be expanded with remote
addressable NAC power boosters and programmed with
specific activation patterns.
The standard control panel includes one SLC that
supports 254 addressable points (254 analog detectors or
modules, or 127 analog sounder bases in combination
with a suitable detector). The control panel is easily
expandable with the FPE‑1000‑SLC Signaling Line Circuit
Plug-in Module, doubling the address points to 508.
The panel has a compact and solid metal housing with a
keyed lock and a removable dead front door to access
electronics. It features surface and semi-flush mounting
options. On the front of the panel, six light-emitting
diodes (LEDs) show Fire, Carbon Monoxide (Gas) Alarm,
Power, Supervisory, Silenced, and Trouble conditions. The
built‑in keypad can be used for total system control and
programming even when wearing fireman gloves. In
addition, a large 4‑line by 20‑character alphanumeric LCD
display shows programmed device point information. Four
keys enable Drill, Reset, Silence, and Acknowledge
functions.
The FPA‑1000‑UL enables various programming
approaches:
•
Front panel programming
•
On-site programming, using a laptop with the
possibility of pre-programming at the office
•
Off-site programming, with remote access via Ethernet
(browser-based).
Front panel programming provides an auto‑learn function,
allowing the installer to configure the system quickly and
easily in default mode. Using a local laptop or remote
access communication, the programming is carried out by
means of a browser‑based user interface. Therefore, no
software installation is required. The panel can receive
diagnostics from a Web browser running on a networked
PC.
FPA‑1000‑UL Analog Addressable Fire
Panel
▶
Support for up to 508 points on two analog
addressable loops
▶
Built‑in Ethernet connector for web‑browser based
programming and ConettixIP Alarm-over-IP
communication
▶
Carbon Monoxide Detector (gas) support meets
NFPA 720 (2009) requirements for visual and audible
annunciation
▶
Auto‑Learn mode for easy provisioning
▶
On‑line help and off‑line programming capability
provide simple configuration and service
www.boschsecurity.com