16 en | Installation Access Control Interface Module
F.01U.215.244 | 05 | 2012.06 Installation and Operation Guide Bosch Security Systems, Inc.
Figure 3.2 Terminal locations
Point Sensor Loop. Install a 1 kΩ resistor at the door contact, not at the terminal of the input.
This will provide supervision against grounds on the loop. Connect only one contact, that
being the door, to this input.
Point Tolerance. Section Table 3.2 Point Tolerance Voltages, page 17 shows the voltages
that determine the condition of the on-board point. Use the point common as your (-)
reference when measuring the point (+). Set your meter for 10 to 24 VDC range.
Callout Description Callout Description Callout Description
1 PWR 8 T+ 15 5.2V
2A 9COM16DATA0
3 B 10 ZN+ 17 DATA1
4 COM 11 RTE 18 BUZZER
5NC 12COM19LED
6C 13REX
7 NO 14 12V
NOTICE!
See the D9210C Access Interface Module Program Entry Guide for assigning a point to the door
controller and the control panel Program Entry Guide for the point types.