Bosch Security Systems, Inc. UL Installation Instructions F.01U.167.105 | 02 | 2010.11
4.1 Terminal Wiring Requirements
Battery
Discharge/
Recharge
Schedule
Discharge
Cycle
13.9 VDC Charging float level.
13.8 VDC Charging status LED on.
12.1 VDC Low Battery and AC Fail Reports if programmed. Low Battery LED
on.
10.2 VDC Minimum operational voltage.
10.0 VDC Battery load shed (processing functions continue if AC is
present).
Recharge
Cycle
AC ON Load shed relay resets, battery charging begins, Battery Trouble
and AC Restoral Reports sent.
13.7 VDC Battery Restoral Report sent, Low Battery LED off.
13.9 VDC Charging status LED off, battery float charged.
Environmental Temperature: 0°C to +50°C (+32°F to +122°F)
Relative
Humidity:
Maximum 93% non-condensing
Arming
Stations
D720/D720B Keypads, D1255/D1255B/D1255RB Keypads, D1256/D1256RB Fire Command
Centers; D1257/D1257RB Fire Alarm Annunciators; D1260/D1260B Keypads; Keyswitch
Point
Thresholds
On-board
Points 1 to 8
Open
Normal
Short
Greater than 3.7 VDC, but less than 5.0 VDC. Greater than 2.0
VDC, but less than 3.0 VDC. Greater than 0.0 VDC, but less than
1.3 VDC.
Compatible
Enclosures
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40
Battery Box
Terminal
No
Terminal
Description
Requirements
1 AC 18 AWG min (up to 14 AWG max)
2 AC 18 AWG min (up to 14 AWG max)
3 + AUX POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
4 BATTERY - Bosch supplied wire lead, included with panel
5 BATTERY + Bosch supplied wire lead, included with panel
6 RELAY A Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
7 RELAY B Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
8 RELAY C Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
9 COMMON Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
10 EARTH
GROUND
14 to 16 AWG
11 POINT 1 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
12 POINT 1/2
COMMON
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
13 POINT 2 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
14 POINT 3 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω