D9412GV2/D7412GV2 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 73
Figure 42: D7412GV2, Input Points and Peripheral Devices
Sw. Aux Pwr
Zone B
Zone A
Pnl Common
Pnl Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
Aux Power
Zone B
Zone A
Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
11
12
13
Loop A+
Loop A-
Loop B+
Loop B-
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
GROUND FAULT DETECT
Enabled
Disabled
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
+
-
TELCO
RING
TIP
PHONE LINE
SEIZED
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO CORD
MODEL D161
PROGRAMMABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and
67
Terminal
8
D7412GV2
1 - (Optional): For 24 V applications use a UL Listed
24 VDC power supply with a D130 Relay Module.
Refer to the D130 Installation Instructions (P/N:
74-06262-000) for correct wiring requirements.
2 - D130 Relay Module
3 - D125B Powered Loop Interface Module
4 - To UL Listed 2-wire smoke detectors. Refer to
Two-Wire Smoke Detectors in the D7212GV2
Approved Applications Compliance Guide
(P/N: F01U003806) for a listing of compatible
two-wire smoke detectors.
5 - P105F 1 k EOL resistor (P/N: 14-03130-004):
Suitable for non-powered initiating and
supervisory devices such as pull stations, heat
sensors, and valve tampers.
6 - P105BL1 1k EOL resistor (P/N: 16179B): For
typical burglar alarm applications.
7 - D129 Dual Class A Initiation Circuit Module:
Provides optional Waterflow Alarm Retard
feature. Not suitable for two-wire smoke
detectors.
All external connections except Terminal 5 (battery positive) are power limited.