D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 Installation
16 Bosch Security Systems, Inc. | 2/10 | F01U143070-01
4.2 Enclosure Options
Mount the control panel assembly in any of the Bosch
Security Systems, Inc. enclosures listed:
• D8103 Universal Enclosure (tan)
• D8109 Fire Enclosure (red)
• D8108A Attack Resistant Enclosure (tan)
Refer to the D9412GV3/D7412GV3 Approved
Applications Compliance Guide (P/N: F01U143069) to
determine if the application requires a specific
enclosure.
4.3 Mounting Enclosure
1. Run the necessary wiring throughout the
premises.
2. Mount the enclosure in the desired location. Use
all five enclosure mounting holes. Refer to
Figure 2.
3. Pull the wires into the enclosure.
Electromagnetic interference (EMI) can
cause problems on long wire runs.
Figure 2: Enclosure Mounting
8
2
1
3
2
4
3
7
5
9
6
1 - Point chart label
2 - Mounting skirt hooks (2)
3 - Module mounting holes (12)
4 - Tamper switch mounting holes (5)
5 - Skirt mounting hole (1)
6- Enclosure mounting holes (5)
7 - Mounting skirt hook holes (2)
8 - Back of D9412GV3/D7412GV3 Control Panel
9 - Lock down tab
4.4 Installing the Control Panel
1. Place the control panel over the inside back of the
enclosure, aligning the large rectangular openings
of the mounting skirt with the mounting hooks of
the enclosure. Slide the control panel down so
that it hangs on the hooks. Refer to Figure 2, Item
2 on page 16.
2. Remove the tape from the #6 x 1/4-in. screw in
the mounting tab on the control panel. The screw
passes through the mounting tab and into the
skirt mounting hole in the enclosure. Tighten the
screw to secure the control panel in the
enclosure.
3. Connect earth ground to the control panel before
making any other connections. Refer to Section
4.5 Connecting Earth Ground.
4.5 Connecting Earth Ground
4.5.1 Terminal 10
To help prevent damage from electrostatic charges or
other transient electrical surges, connect the system
to earth ground at Terminal 10 before making other
connections. Recommended earth ground references
are a grounding rod or a cold water pipe.