74-07692-000-C 4/97D9000/D7000 Series Control/CommunicatorOperation and Installation Manual
D9000/D7000 Series Operation & Installation ManualPage 1074-07692-000-C 4/97Listings and ApprovalsThe D9000/D7000 Literature Pack includes the
D9000/D7000 Series Operation & Installation ManualPage 1174-07692-000-C 4/97InstallationBefore You BeginThis Installation section contains a ge
D9000/D7000 Series Operation & Installation ManualPage 1274-07692-000-C 4/97Installing the Assembly1. Place the assembly over the inside back
D9000/D7000 Series Operation & Installation ManualPage 1374-07692-000-C 4/97Instructions for wiring the off-board point POPITsensor loops are f
D9000/D7000 Series Operation & Installation ManualPage 1474-07692-000-C 4/97Testing the SystemAfter finishing the installation and programming
D9000/D7000 Series Operation & Installation ManualPage 1574-07692-000-C 4/97Power SupplyPrimary PowerTerminals 1 2Primary (AC) Power CircuitA 1
D9000/D7000 Series Operation & Installation ManualPage 1674-07692-000-C 4/97D8132 boosts battery backup: Adding a D8132Battery Charger Module
D9000/D7000 Series Operation & Installation ManualPage 1774-07692-000-C 4/97Charging Status and Low Battery LEDsCharging Status LED (Yellow)The
D9000/D7000 Series Operation & Installation ManualPage 1874-07692-000-C 4/97Power OutputsCircuit ProtectionThree self-resetting thermal circuit b
D9000/D7000 Series Operation & Installation ManualPage 1974-07692-000-C 4/97The Radionics defaults set relay A (terminal 6)as a Steady Alarm Bel
D9000/D7000 Series Operation & Installation ManualPage 274-07692-000-C 4/97PrefaceThis manual addresses the operation andinstallation of the D
D9000/D7000 Series Operation & Installation ManualPage 2074-07692-000-C 4/97Relay InstallationPower down the system before inserting theD136 rela
D9000/D7000 Series Operation & Installation ManualPage 2174-07692-000-C 4/97Telephone ConnectionsRegistrationThe Radionics D9412, D9112, D7412,
D9000/D7000 Series Operation & Installation ManualPage 2274-07692-000-C 4/97The panel stops monitoring the phone line duringits phone line troubl
D9000/D7000 Series Operation & Installation ManualPage 2374-07692-000-C 4/97Set the ring count above 2 on answeringmachines: The line's RA
D9000/D7000 Series Operation & Installation ManualPage 2474-07692-000-C 4/97D928 Status LEDsFour LEDs mounted on the front edge of theD928 module
D9000/D7000 Series Operation & Installation ManualPage 2574-07692-000-C 4/97On-Board PointsPoint ParametersYou can determine the condition of on
D9000/D7000 Series Operation & Installation ManualPage 2674-07692-000-C 4/97Off-Board PointsPoint (ZONEX) BusD9412/D9112 Terminals 23 to 28D741
D9000/D7000 Series Operation & Installation ManualPage 2774-07692-000-C 4/97GNDAUXINOUT-++-LOOPON0654321DATA+-D9127U/T-++-LOOPON0654321DATA+-D91
D9000/D7000 Series Operation & Installation ManualPage 2874-07692-000-C 4/97Installing the D8125 POPEX ModuleSave the POPIT Label Sheets: The D
D9000/D7000 Series Operation & Installation ManualPage 2974-07692-000-C 4/97Wiring Data Expansion Loops to POPEXModulesThere are two positive (+
D9000/D7000 Series Operation & Installation ManualPage 374-07692-000-C 4/97FCC NoticesPart 15This equipment has been tested and found tocomply
D9000/D7000 Series Operation & Installation ManualPage 3074-07692-000-C 4/97POPIT LabelsOff-board points for the D9412 and D9112 arenumbered 9
D9000/D7000 Series Operation & Installation ManualPage 3174-07692-000-C 4/97Wiring OctoPOPITsFollow the procedure below to wire D8128COctoPOPIT
D9000/D7000 Series Operation & Installation ManualPage 3274-07692-000-C 4/97Control/CommunicatorPanel282726252423TO CONTROL1234567 8910 11 1213
D9000/D7000 Series Operation & Installation ManualPage 3374-07692-000-C 4/97Table 3: D8128C OctoPOPIT Address Switch SettingsNOTES:a. Dipswitch
D9000/D7000 Series Operation & Installation ManualPage 3474-07692-000-C 4/97Off-Board RelaysD8129 OctoRelayThe D8129 OctoRelay allows you to ad
D9000/D7000 Series Operation & Installation ManualPage 3574-07692-000-C 4/97D811 Arm Status Relay ModuleThe D811 Arm Status Relay Module allow
D9000/D7000 Series Operation & Installation ManualPage 3674-07692-000-C 4/97InstallationYou can install the D811 in the enclosure with thepanel
D9000/D7000 Series Operation & Installation ManualPage 3774-07692-000-C 4/97Arming DevicesDescriptionCommand Centers, maintained or momentaryc
D9000/D7000 Series Operation & Installation ManualPage 3874-07692-000-C 4/97Switching the green and yellow wires affectsother Command Centers:
D9000/D7000 Series Operation & Installation ManualPage 3974-07692-000-C 4/97KeyswitchDescriptionYou can connect a maintained or momentaryconta
D9000/D7000 Series Operation & Installation ManualPage 474-07692-000-C 4/97Table of ContentsBattery Discharge/Recharge Schedule ... 16Cha
D9000/D7000 Series Operation & Installation ManualPage 4074-07692-000-C 4/97SDI DevicesDescriptionThe panel can support a number of accessoryde
D9000/D7000 Series Operation & Installation ManualPage 4174-07692-000-C 4/97D9210B Access Control ModuleThe Radionics D9210B Access Control In
D9000/D7000 Series Operation & Installation ManualPage 4274-07692-000-C 4/97Programmer and Accessory ConnectionsProgrammer Connector (J7)The pr
D9000/D7000 Series Operation & Installation ManualPage 4374-07692-000-C 4/97D9412 FACEPLATE5910142Low Batter yLEDs Off When NormalEARTH GROUND
D9000/D7000 Series Operation & Installation ManualPage 4474-07692-000-C 4/97Quick Reference Terminal DescriptionTerminal Name Description1, 2 C
D9000/D7000 Series Operation & Installation ManualPage 4574-07692-000-C 4/97Troubleshooting GuideIntroductionRadionics provides this guide to
D9000/D7000 Series Operation & Installation ManualPage 4674-07692-000-C 4/97SERVC KEYPAD - Supervised CommandCenter MissingWhen the panel los
D9000/D7000 Series Operation & Installation ManualPage 4774-07692-000-C 4/97Communications FailureThe panel goes into Communications Failureaf
D9000/D7000 Series Operation & Installation ManualPage 4874-07692-000-C 4/97Problems Programming the PanelBefore attempting to program the pane
D9000/D7000 Series Operation & Installation ManualPage 4974-07692-000-C 4/97Problems with Points (Continued)Symptom Diagnosis RemedyOne or mor
D9000/D7000 Series Operation & Installation ManualPage 574-07692-000-C 4/97Wiring Data Expansion Loops toPOPEX Modules ...
D9000/D7000 Series Operation & Installation ManualPage 5074-07692-000-C 4/97Problems with the D8125 POPEX DataExpansion LoopsEMI (Electro-magne
D9000/D7000 Series Operation & Installation ManualPage 5174-07692-000-C 4/97Problems with Command CentersSymptom Diagnosis RemedyCommand cente
D9000/D7000 Series Operation & Installation ManualPage 5274-07692-000-C 4/97Runaway Reports to the ReceiverUsing the D8128 or D8128A in place o
D9000/D7000 Series Operation & Installation ManualPage 5374-07692-000-C 4/975. During the Service Walk Test you may wantto see the points that
D9000/D7000 Series Operation & Installation ManualPage 5474-07692-000-C 4/97Approved Applications Compliance GuideListings and ApprovalsFireULU
D9000/D7000 Series Operation & Installation ManualPage 5574-07692-000-C 4/97For battery calculations, refer to Current RatingChart for Standby
D9000/D7000 Series Operation & Installation ManualPage 5674-07692-000-C 4/97System ChartHousehold BurglaryHousehold FireHousehold Fire/Burglary
D9000/D7000 Series Operation & Installation ManualPage 5774-07692-000-C 4/97System Wiring Diagrams, Issue APPPPSD122 DUALBATTERY HARNESSARMING
D9000/D7000 Series Operation & Installation ManualPage 5874-07692-000-C 4/97D9112 Control/CommunicatorPPPPSD122 DUALBATTERY HARNESSARMING STATI
D9000/D7000 Series Operation & Installation ManualPage 5974-07692-000-C 4/97D7412 Control/CommunicatorPPPPSD122 DUALBATTERY HARNESSARMING STATI
D9000/D7000 Series Operation & Installation ManualPage 674-07692-000-C 4/97Figures and TablesFigure 1: System Configuration ...
D9000/D7000 Series Operation & Installation ManualPage 6074-07692-000-C 4/97D7212 Control/CommunicatorPPPPSD122 DUALBATTERY HARNESSARMING STATI
D9000/D7000 Series Operation & Installation ManualPage 6174-07692-000-C 4/97Current Rating Chart for Standby Battery CalculationsABCAC Power On
D9000/D7000 Series Operation & Installation ManualPage 6274-07692-000-C 4/97Standby Battery RequirementsHousehold Burglary and CommercialBurgla
D9000/D7000 Series Operation & Installation ManualPage 6374-07692-000-C 4/97Standby Battery Calculation forNFPA 72 Fire Alarm ApplicationsCurre
D9000/D7000 Series Operation & Installation ManualPage 6474-07692-000-C 4/97Battery Discharge/Recharge ScheduleDischarge Cycle13.9 VDC Charging
D9000/D7000 Series Operation & Installation ManualPage 6574-07692-000-C 4/97Point ThresholdsOn-Board Points 1 to 8Voltage ResistanceNormal 2.3
D9000/D7000 Series Operation & Installation ManualPage 6674-07692-000-C 4/97Appendix: Point Address ChartZONEX 1, Points 9 to 127 (D9412/D9112)
ZONEX 2, Points 129 to 247 (D9412/D9112 Only)A number in the switch column indicates that switch is set to ON.Switch Switch SwitchAddress0123456Addres
D9000/D7000 Series Operation & Installation ManualPage 774-07692-000-C 4/97IntroductionFigure 1: System Configuration Control/CommunicatorD
D9000/D7000 Series Operation & Installation ManualPage 874-07692-000-C 4/97CommunicatorThe Control/Communicator uses a built-in digitalcommuni
D9000/D7000 Series Operation & Installation ManualPage 974-07692-000-C 4/97EMI/Lightning Transient ProtectionThe D9000/D7000 Series Control/Com