D9412GV2/D7412GV2
D9412GV2/D7412GV2 Release Notes for Version 7.05
F01U003637-02 Page 4 © 2007 Bosch Security Systems, Inc.
Corrections now prevent a duress passcode from
being accepted by a keypad currently in an area
that has
A# Duress Enable
set to No. If the
Duress feature is used, A
# Duress Enable
should
be set to Yes for all areas.
The alternate function of Area 6 Silent Alarm
Relay parameter was removed. To enable Fire
Trouble Resound support, use
GV2AUXMISCELLANEOUSFire Trouble
Resound.
The alternate function of Area 5 Silent Alarm
Relay parameter was removed. The Ground Fault
detection feature is solely enabled by closing
Switch S4 on the D9412GV2 and D7412GV2
Control Panels.
Changes now suppress the ALARM SILENCED
message when a user attempts to silence a Ring
Until Restored fire bell. A fire alarm generated by
a point with the Ring Until Restored (
P# Ring Til
Rst
) feature set to Yes will sustain the fire bell
until the sensor is restored.
Corrections ensure that acknowledged Silent
Alarms scroll correctly on the idle text displays on
the D1260 and D1260B Keypads.
Corrections now allow a user’s token, with
L#
Disarm Level
set to I, to disarm the interior of all
areas within the scope of the keypad programmed
at
D# CC# Scope
. The keypad programmed at
D# CC# Scope
must have
CC# Passcode
Follows Scope
set to Yes to disarm the interior of
all areas within scope.
Corrections now allow the panel-wide
Communications Failure Relay output to activate
when events in Route Groups 2 through 4 do not
reach the central station. Previously this relay
output activated only on a communication failure
for Route Group 1.
2.3 Version 7.02
The Phone Line Supervision feature has improved
accuracy in detecting the phone line.
The Modem IIIa
2
product ID is changed to the
same ID as the G Series control panels, allowing
compatibility with non-Bosch central station
receivers.
2.4 Version 7.01
The following are corrections and changes made since
Version 6.60 in the G Series Control Panels.
The GV2 Series Control Panels have the same
response to low AC voltage as to an AC failure.
If the control panel battery is detected as missing,
the Walk Test function skips the Battery Test.
Several system stability issues are fixed to prevent
erroneous Parameter Checksum Failures.
The Service Walk Test on the D7412GV2 and
D7212GV2 now shows the correct maximum
number of points in the system.
The Telephone Ground Start circuitry and
associated programming prompts are removed
from the GV2 Series Control Panels.
The GV2 Series Control Panels require the D6500
receiver to have a D6511 MPU card at version
1.06 or above for maximum communication
efficiency.
The Extend Close (COMMAND 51) feature was
modified to prevent the new Close Window time
from setting to a value earlier than the current
time.
When disarming an area with Two Man Rule
enabled, the keypad waits for the time equal to the
exit delay for the area. If the second passcode is
not entered before the prompt times out, then the
rule resets and waits for the first passcode again.
Several changes in this release prevent local alarm
events from being sent intermittently to the central
station. All local alarm events should now remain
local.