OIL HEATSLAVE26/32CONVENTIONAL FLUE AND ROOM SEALED BF FLOORSTANDING COMBINATION BOILER FOR CENTRALHEATING AND MAINS FED DOMESTIC HOT WATERINSTALLATIO
10FLUE GUARDX = 180 mm MaximumX = 327 mm MaximumOne extension kit – X = 638 mm MaximumTwo extension kits – X = 952 mm Maximum766 mmXX340 mm270 mmFig.
Where bends are necessary, a maximum of two are permittedand 135° bends should be used.All brick and masonry chimneys should be lined with a suitablen
127.4 Siting the flue terminal 1. The flue terminal must be located in a suitable position, asshown in Fig 8, such that products of combustion can be
(See Figs. 10, 11 and 12). 8.1 The oil storage tank must be installed in accordance withBS799: part 5. The tank should be arranged with a slope of 1 i
14Fig. 11. Oil Supply.(a) Single pipe systemOil tankOil tankSludge cockMaximum oil levelH = 4 m (13 ft) maximumH = 3.5 m (11.5 ft) maximumTank raised
159.1 The appliance incorporates a circulating pump. No otherpump is required. The appliance will operate satisfactorily on atwo-pipe small bore or
16Where the system volume exceeds the value given in Table 11 anadditional expansion vessel, of suitable volume, should be fittedto the heating return
17The following points are for guidance only. The systeminstallation should be carried out in accordance with BS 5449.Part 1.11.1 The feed and expansi
18Refer to Figs. 16, 17, 18 and 19.13.1 The wiring between the appliance and the electrical supplyshall comply with current IEE Wiring Regulations and
19Fig. 17. Schematic Electrical Diagram.Fig. 18. Room and Frost ThermostatConnectionsFig. 19a. Facia Mounted ProgrammerConnections.LOCKOUTINDICATORMOT
21. Installation Regulations...Page 22. General Information ...
20The mains supply cable should be connected into the mainsconnection points on the control board marked L (Live), N(Neutral) and E (Earth) on the con
2114. Functional Flow ChartCENTRAL HEATING AND DOMESTICHOT WATER MODE(HEATING ON and HOT WATER ON selected)YESNOPump water to theHeatslave tank. Burne
22DOMESTIC HOT WATER MODE ONLY(HOT WATER ON selected)YESNOPump water to theHeatslave tank.Burner on. Pump on.Diverter valve off.Domestic hot waterdema
23CENTRAL HEATING MODE ONLY(HEATING selected on programmer)Domestic hot waterdemand via tap orshower.Has the boiler high limitthermostat activated?Is
2415.1 After unpacking the appliance it is recommended that allcabinet panels are removed, as described in Section 5, andstored in a safe place to avo
2515.6 Oil supply installation.(See Fig. 10 to 12).NOTE: Never route the oil supply pipe/hose directly below thecombustion chamber base.(a) Double pip
2616.6 Check the installation.1. Check that the appliance is correctly wired as described inSection 13.2. Check that all baffles are correctly located
2717.1 Hand the Users Instructions to the user or purchaser forretention; instruct them in the efficient and safe operation of theappliance and the he
28Fig. 21. Electro Oil Sterling 40 Burner.TransformerConnectingpipeSolenoidvalveAir controlindicatorPressureadjustmentscrewAir adjustmentscrewMotorCom
292. With the sponge O-ring gasket around the burner blast tubeinsert the burner into the housing tube. Push the burner firmlyforward to compress the
3Flow SwitchThe domestic mains water inlet is connected to a flow switchwhich detects when a domestic hot water tap has been opened.This activates the
NOTE: A residue of water will remain in the diverter valve.Open the valves and fill the system as described in Section 16.4. Heatslave TankCheck that
Carefully withdraw the electrical box and temporarily seat in asuitable place such as the top of the boiler.Reasemble the electrical box in reverse or
3220. Short Parts ListPart Manufacturers Reference Qty WHS Part No.Burner Control 1. Box Satronic TF832C.3 1 8 716 156 648-0Photocell Satronic MZ770 1
33LOCKOUTINDICATED BY RED LAMP ON CONTROL BOXTo Re-set wait 2 minutes and press re-set buttonIgnition failure No oil deliveryfrom nozzle.Check oil sup
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in
OIL HEATSLAVE12/14 15/19 20/25CONVENTIONAL FLUE AND ROOM SEALED BF FLOORSTANDING COMBINATION BOILER FOR CENTRALHEATING AND MAINS FED DOMESTIC HOT
21. Installation Regulations ...Page 22. General Information ...
3Flow SwitchThe domestic mains water inlet is connected to a flow switchwhich detects when a domestic hot water tap has been opened.This activates the
4SPECIFICATIONSModel 26/32POWER SUPPLY 230V/240V 50 HzHEATING FLOW 28mmHEATING RETURN 11/4 " BSPCOLD WATER MAINS INLET 15mmDOMESTIC HOT WATER OU
4SPECIFICATIONSModel 12/14 15/19 20/25POWER SUPPLY 230V/240V 50 Hz 230V/240V 50 Hz 230V/240V 50 HzHEATING FLOW 22mm 22mm 22mmHEATING RETURN 1in. BSP 1
5* NOTE: For use on conventional flue only.** NOTE: The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe
64.1 The appliance is not suitable for external installation unlessa suitable enclosure is provided.4.2. The appliance should be positioned on a non c
7Fig.3. Conventional Flue Appliance (CF/LLD).Control Box AssemblyFront panelBurnerThermostat knobElectrical control boxControl box top coverUser opera
8Fig.4. Room Sealed Balanced Flue Appliance (RS).Control Box AssemblyFront panelBurnerBurner coverThermostat knobElectrical control boxControl box top
OPEN FLUE MODEL (CF/LLD)This includes conventional flue and standard low level and highlevel horizontal discharge kits.6.1 In order to ensure clean an
10FLUE GUARDX = 180 mm MaximumX = 327 mm MaximumOne extension kit – X = 638 mm MaximumTwo extension kits – X = 952 mm Maximum766 mmXX340 mm270 mmFig.
11The flue should be vertical and contain as few bends as possible.Where bends are necessary, a maximum of two are permittedand 135° bends should be u
127.4 Siting the flue terminal 1. The flue terminal must be located in a suitable position, asshown in Fig 8, such that products of combustion can be
13(See Figs. 10, 11 and 12). 8.1 The oil storage tank must be installed in accordance withBS799: part 5. The tank should be arranged with a slope of 1
5* NOTE: For use on conventional flue only.** NOTE: The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe
14Fig. 11. Oil Supply.(a) Single pipe systemOil tankOil tankSludge cockMaximum oil levelH = 4 m (13 ft) maximumH = 3.5 m (11.5 ft) maximumTank raised
159.1 The appliance incorporates a circulating pump. No otherpump is required. The appliance will operate satisfactorily on atwo-pipe small bore or
16Where the system volume exceeds the value given in Table 11 anadditional expansion vessel, of suitable volume, should be fittedto the heating return
17The following points are for guidance only. The systeminstallation should be carried out in accordance with BS 5449.Part 1.11.1 The feed and expansi
18Refer to Figs. 16, 17, 18 and 19.13.1 The wiring between the appliance and the electrical supplyshall comply with current IEE Wiring Regulations and
19Fig. 17. Schematic Electrical Diagram.Fig. 18. Room and Frost ThermostatConnectionsFig. 19a. Facia Mounted ProgrammerConnections.LOCKOUTINDICATORMOT
20The mains supply cable should be connected into the mainsconnection points on the control board marked L (Live), N(Neutral) and E (Earth) on the con
2114. Functional Flow ChartCENTRAL HEATING AND DOMESTICHOT WATER MODE(HEATING ON and HOT WATER ON selected)YESNOPump water to theHeatslave tank. Burne
22DOMESTIC HOT WATER MODE ONLY(HOT WATER ON selected)YESNOPump water to theHeatslave tank.Burner on. Pump on.Diverter valve off.Domestic hot waterdema
23CENTRAL HEATING MODE ONLY(HEATING selected on programmer)Domestic hot waterdemand via tap orshower.Has the boiler high limitthermostat activated?Is
64.1 The appliance is not suitable for external installation unlessa suitable enclosure is provided.4.2. The appliance should be positioned on a non c
2415.1 After unpacking the appliance it is recommended that allcabinet panels are removed, as described in Section 5, andstored in a safe place to avo
2515.6 Oil supply installation.(See Fig. 10 to 12).NOTE: Never route the oil supply pipe/hose directly below thecombustion chamber base.(a) Double pip
2616.6 Check the installation.1. Check that the appliance is correctly wired as described inSection 13.2. Check that all baffles are correctly located
2716.20 Completion of CommissioningIf the appliance is being passed over to the user immediately,refer to Section 17 and set the controls to the users
Combustion headLocking screwTransformerPhotocellControl boxLockout reset buttonAir adjustment screwAir control indicator(4mm hexagonal head)Oil pumpPr
297. Replace the combustion head. Check that the nozzle liescentral to the combustion head and the head settings are asshown in Figs. 21 and 22.8. Wit
304. Reconnect the electrical lead plug into the control box. 5. Turn on the oil supply at the service cock.6. Recommission the burner as described in
fitting from the tank.Raise the front end of the tank sufficiently to clear the base lipand withdraw the tank.Remove the remaining components from the
Remove the heyco split bush and slide the copper capillary tubethrough the slot, freeing the capillary tube from the electricalcontrol box.Remove the
33LOCKOUTINDICATED BY RED LAMP ON CONTROL BOXTo Re-set wait 2 minutes and press re-set buttonIgnition failure No oil deliveryfrom nozzle.Check oil sup
7Fig.3. Conventional Flue Appliance (CF/LLD).Electrical Box AssemblyFront panelBurnerThermostat knobControl boardElectrical box top coverUser operatin
34
35
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in
AMENDMENT SHEET TO MEET THE REQUIREMENTS OFAMENDED BUILDING REGULATIONS DOCUMENT JTHE FIGURES, INFORMATION & DIAGRAMS INCLUDED IN THIS AMENDMENT S
RS FLUETERMINAL KITFOR USE ON ALL DANESMOOR ROOM SEALEDBF OIL-FIRED APPLIANCESINSTALLATION INSTRUCTIONSTHESE INSTRUCTIONS APPLY IN THE UK ONLYTHESE IN
It is essential that the boiler is commissioned and serviced by acompetent engineer.Worcester Heat Systems Limited will be pleased to offer regularser
4.1 Remove the rear air duct top cover by undoing the two screws.4.2 Fit the locking band. (See Fig. 1).1. Slide the locking band over the clamping co
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in
Bosch ThermotechnikMULTI-DIRECTIONALBALANCED FLUE KITINSTALLATIONINSTRUCTIONSFOR USE ON DANESMOOR ROOM SEALEDB.F. OIL-FIRED APPLIANCESTHESE INSTRUCTIO
1.1 These instructions should be read in conjunction with therelevant parts of the boiler Installation and ServicingInstructions, RS Flue Terminal Ins
8Fig.4. Room Sealed Balanced Flue Appliance (RS).Electrical Box AssemblyFront panelBurnerBurner coverThermostatknobControl boardElectrical box topcove
3.28 Loosely fit the three stainless steel bolts (I) into the fluecollar assembly from beneath the boiler flue outlet plate. SeeFigs 2 and 4.3.29 Alig
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in
TWIN CHANNEL PROGRAMMER FITTINGAND OPERATING INSTRUCTIONSGeneral information is given in the users instruction leaflet despatched withthe appliance an
Gas Safety (Installation and Use) Regulations 1984: All gas appliances must be installed by acompetent person, in accordance with the above regulation
ELECTRICAL CONNECTIONS3Highflow 400Highflow 400 ElectronicDanesmoor Oil BoilerOil HeatslaveX12CHLNDHWCHLNDHWX2
The programmer controls the hot water and central heating functions independently.When a CENTRAL HEATING programme is selected, the appliance will ope
STANDARD PROGRAMMESWITCHING Mon.-Fri. Sat.-Sun.CH HW CH HWON1 6.30 a.m. 6.30 a.m. 7.00 a.m. 7.00 a.m.OFF1 8.30 a.m. 8.30 a.m. 9.00 a.m. 9.00 a.m.ON2 4
You can now enter CH operating times for MONDAY only if required.Press YES until Time, ON appears.Press – and + buttons to set the time and continue a
Holiday SettingPress SET until SET H’DAY? appears.Press YES and 00 will appear.Press – and + buttons to set the number of days you require the system
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specificationsand/or appearances are changed in t