Bosch D1255RB Bedienungsanleitung Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 30
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
7.0 Current Ratings Charts
.
Bosch Security Systems, Inc. | 3/12 | F01U266055-01 23
7.2 Standby Battery Calculations
UL 365 requires 72 h of standby battery capacity. Limit the auxiliary power current for all devices,
including keypads, to 300 mA or less to meet this requirement.
Table 6: Standby Battery Requirements
Type Required Capacity Calculations
Household Burglary and
Commercial Burglary
4 h
Bank Safe and Vault
72 h (UL 365). Auxiliary power
current for all devices, including
keypads, must be limited to 300 mA
or less to meet this requirement.
Central Station or Local Fire Alarm 24 h + 5 min of alarm operation.
Remote Station or Auxiliary Fire
Alarm
60 h + 5 min of alarm operation.
Household Fire Warning
Equipment
24 h + 4 min of alarm operation.