
GV4 Series | Approved Applications Compliance Guide | 2.0 Optional Compatible Equipment
Bosch Security Systems, Inc. | 3/12 | F01U266055-01 9
2.3.5 Other Devices
Use a D130 Relay Module, D8129 OctoRelay, or
Switched Aux (Terminal 8) to provide reset
capability to other initiating devices such as:
D125B Powered Loop Interface Module (2-
wire smoke detector module)
D129 Dual “Class A” Initiation Circuit
Module (4-wire smoke detector)
D9127T/U POPITs
On-board points
Install devices according to the manufacturer’s
instructions. Refer to Off-Board Relays in the
D9412GV4/D7412GV4/D7212GV4 Installation
and Operation Guide (P/N: F01U201527).
For battery calculations, refer to Table 7 on
page 24 and Section 8.0 NFPA 72 Fire Alarm
Applications on page 26.
Test Weekly: Perform a Fire Test
weekly. Both the AC power and
battery are tested according to UL
864
(D9412GV4/D7412GV4/D7212GV4)
Kommentare zu diesen Handbüchern