Table 6: Troubleshooting
Transmitter
LED Condition Solution
Flashing Normal
Off 1. There is no power at the transmitter.
2. The
Aim Mode
button not pressed.
3. The transmitter is faulty.
1. Restore power to Terminals 1 and 2.
2. Press the
Aim Mode
button.
3. Replace the transmitter.
Receiver – Aim Mode
Red
LED
Yellow
LED
Green
LED
Terminals
4 and 5
Terminals
6 and 7
Condition Solution
On On Flashing Open Open The alignment is acceptable.
On On On Open Open The beam is blocked or the
receiver is misaligned.
Clear the beam path or
realign the receiver.
On Flashing Flashing Open Open The sensitivity setting is invalid. Set the receiver to the
proper setting.
On Off Off Open Open There is no power. Check for power at
Terminals 8 and 9.
Receiver - Normal Mode
Off Off On Open Closed The receiver is initializing. It
stabilizes in 60 sec to 120 sec
Off Off On Open Open The receiver is initializing. The
access door is missing or
loose.
Replace the access
door.
Off Off Flashing Open Closed Normal.
Off Off Flashing Open Open The access door is missing or
loose.
Replace the access
door.
Off On On Open Open Trouble. Beam is blocked or
misaligned.
Clear the beam path or
realign the receiver.
Off On Flashing Open Open Trouble. If the reference voltage
is less than 2 VDC, dust on the
lens reduced the signal
strength or vibration misaligned
the receiver.
Clean the transmitter
and receiver covers. If
the reference voltage
does not return to 4
VDC, realign the receiver
and press the Setup
switch.
Off On Flashing Open Open If the reference voltage is
greater than 4.8 VDC, the
beam strength increased
because an initial beam
misaligned or a partial blockage
was removed at setup.
Perform a fine-tune
alignment of the receiver
and use the
Setup
button.
On Off Flashing Closed Closed Alarm. Determine the cause of
the alarm and reset the
receiver.
On Off Flashing Closed Open Alarm. The access door is
missing or loose.
Determine the cause of
the alarm and reset the
receiver. Replace the
access door.
On On On Closed Open Alarm and Trouble. An alarm
occurred, then the beam was
blocked.
Determine the cause of
the alarm and reset the
receiver. Clear the beam
path.