Bosch DS7200V2-EXP Betriebsanweisung Seite 108

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 156
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 107
DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 108
Bosch Security Systems | 8/04 | 4998153891C
Bell Time
Address: 1040
Default: 6 (min.)
Selections: 0-15 (1-minute increments)
Bell Time determines how long, 0 to 15 min., the Alarm Output, Fire Alarm Output, Silent Alarm Output, and
Bell Time functions remain activated when triggered by an alarm event.
Siren Warble Frequency
Address: 1041
Default: 7
Selections: 0 (lowest tone/frequency) to 15 (highest tone/frequency)
This parameter sets the siren warble frequency for non-fire alarm output functions.
Programmable Output 2 (PO 2) can be configured as a supervised horn/speaker output (see Global Output Options
on page 107).
This parameter sets the warble frequency for the alarm output functions (1|8, 1|9, 1|10, and 8|8). The setting
chosen here does not apply to other output functions.
Lowering the frequency effectively raises the perceived volume.
Alarm Output Arming Beep Volume
Address: 1042
Default: 7
Selections: 0 (no sound) to 15 (loudest); 1 = quiet)
PO 2 can be configured as a supervised horn/speaker output (see Global Output Options on page 107).
This parameter sets the perceived volume for the Alarm Output Arming Beep.
Seitenansicht 107
1 2 ... 103 104 105 106 107 108 109 110 111 112 113 ... 155 156

Kommentare zu diesen Handbüchern

Keine Kommentare