K2200 DOOR CONTROLLER SERIES
10
The K2200 Series Door Controllers includes the K1200, K2200, K1200IP
and K2200IP door controllers:
The front panel can be used to manage the system in stand-alone mode.
Order slave controllers on network systems without the front panel to
save money on larger systems. Create an access control system with door
controllers, readers, and locks. The power supply supplies power to the
locks and readers.
Features
Manage up to 128 operators and 10,000 cardholders
from a PC-based administration system
Manage up to 32 operators and 4,000 cardholders from stand-alone
mode
Five operating modes
Two K2000/K3000-Series readers or one Wiegand reader for each
door channel
Eight internal relays
10 Mbps Ethernet interface (K2200IP)
Functions
Operating Modes
Stand-alone Mode. Manage the door controllers from the front panel.
Add up to three extra slave controllers, and control up to 16 doors.
Stand-alone mode requires a hard-wired communications link
between the master and the slave controllers
Slave Mode. Configure the door controllers to work as slave
controllers. Manage the slave controllers from another door controller
in stand-alone mode or from a PC-based administration system.
Local Master Mode. Configure the door controllers as local masters.
The local masters connect to the PC directly or through a PC Interface
Kit. Add up to seven additional slave controllers and control up to 32
doors.
Remote Master Mode. This mode is similar to the local master mode;
however, the master door controllers connect to the administration PC
through a Central Network Controller (CNC). CNC communications
occur through hard-wired devices (line drivers or fiber optic
transceivers) over RS-232, or through dial-up modems over PSTN or
TCP/IP.
Dial-up Mode. Program the door controller connected to the remote
site’s modem to dial-back to the CNC during an alarm event or during
selected access granted events.
Local CNC Mode. Each CNC can connect to 32 door controllers and
128 doors at its local site using a hardwired communications link.
Operators
Users can program up to 128 operators.
Door Monitoring
Full door monitoring is built into the door controllers. The door controllers
include inputs for Request-to-exit switches and door contacts. The stand-
alone door controllers can store up to 32 individual time profiles. The door
controllers can store up to 128 individual time profiles. Use these time
profiles to control user access, door operation, and alarms.
Relay Operation
The K2200 Series Door Controllers have eight internal output relays.
Program up to eight relays. PC-based administration software lets users
program a relay to control lighting, operate a video camera, or sound an
alarm.