INST-164 Revision 4
Page 14 of 18
Figure 17: Network Setting Page
This page allows all the relevant network setting to be changed.
Return to Default Setting
In the event that your network settings are lost or incorrect, it is possible to return the Reg-Sentry unit to its
default setting. NB the Reg-Sentry unit is statically sensitive and antistatic precautions should be
observed during the following procedure.
1) Remove the power from the unit and then the lid. Remove the fascia from the unit by unscrewing the
four retaining screws.
2) Place a link across pins 9 and 10 of connector J8.
Figure 18: Link Connection J8
3) Return power to the unit, once the unit has rebooted you will be able to access the network settings as
described above using the IP address 192.168.0.204.
4) Once you have changed the network settings as required (remember to save them), power down the
unit and remove the link from pins 9 and 10 of connector J8.
5) Replace the fascia and lid.