Using interconnect wiring
Interconnect wiring connectors parallel the SDI2 PWR, A, B, and COM terminals on the
terminal strip. In installations with multiple SDI2 modules, using interconnect wiring makes
the installation quicker and easier than using terminal strip wiring. You use any combination of
terminal and interconnect wiring to wire multiple modules in parallel, but do not wire a single
module to the control panel using both terminal and interconnect wiring.
The interconnect wiring connectors are "keyed" (interconnect wiring plug can fit in only one
direction).
PWR A B COM PWR A B COM
TMPR
1 COM 2 7 COM 83 COM 4 5 COM 6
RESET
ETHERNET
COM AUX
R Y G B
PWR A B COM
+ BAT -
18VAC
B C
OUTPUT
NO C NC
OUTPUT A
7 COM 8
C
OUTPUT
B
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
1 k End of Line Resistors
Voltage Ranges
ON-BOARD POINTS
3.7 - 5.0 VDC
2.0 - 3.0 VDC
0.0 - 13 VDC
Open
Normal
Short
3 COM 4 5 COM 61 COM 2
R Y G B
SDI2
Device Bus
18 VAC
BATTERY OUTPUT A
AUX
- 12 V +
OUTPUT A
OUTPUT A
Jumper Under Cover
AUX PWR
COM
DRY
Figure 3.7: SDI2 devices daisy chained with interconnect wiring
Power supply
Primary power terminals
The control panel uses an 18 VAC, 22 VA internally fused transformer (CX4010) for its primary
power source. The control panel draws 125 mA when idle and 155 mA when in an alarm state.
The auxiliary power available for continuously powered devices is 800 mA.
Transient suppressors and spark gaps protect the circuit from power surges. This protection
relies on the ground connection at the earth ground terminal, marked with the
icon. Ensure
that you connect the terminal to a proper ground.
Refer to Connect earth ground, page 9.
AC power fail
The system indicates an AC power failure when the 18 VAC terminals do not have power. The
AC Fail Time parameter sets the number of minutes or seconds without AC power before the
control panel reports the failure, and the number of minutes or seconds after the power
returns before the control panel reports restored power.
Self diagnostics at power up and reset
The system performs a series of self-diagnostic tests of hardware, software, and programming
at power up and at reset. The self-diagnostics tests complete in approximately 10 to 30 sec.
If the control panel fails any test, a System Trouble message appears at the keypads.