Callout ᅳ Description Callout ᅳ Description
6 ᅳ Yellow LINK LED 16 ᅳ SDI2 terminals (power and data)
7 ᅳ Plug-in module retention clip 17 ᅳ Auxiliary power terminals
8 ᅳ On-board Ethernet connector 18 ᅳ Terminals for Output A
9 ᅳ USB connector 19 ᅳ Battery terminals
10 ᅳ Heartbeat LED (blue) 20 ᅳ 18 VAC power input terminals
System wiring diagrams
System wiring overview
Notice!
For UL Certificated accounts, additional power can be obtained using only a UL Listed auxili-
ary 12.0 VDC regulated, power-limited power supply, such as the B520 Auxiliary Power Sup-
ply Module.
All terminals are power limited except BAT+ (battery positive).
All terminals are supervised except OUTPUT A, OUTPUT B, and OUTPUT C.
For proper supervision, do not loop wire under terminals. Break the wire run to provide su-
pervision of connections.
7
7.1
Control Panels Introduction | en 21
UL Installation Instructions 2013.01 | 04 | F01U265448
Kommentare zu diesen Handbüchern