connections, and to assist in field-testing.
Report results in writing.
C. Perform the following field tests and inspections
and prepare reports:
1. Inspection: Verify that units and controls
are properly labeled and interconnecting
wires and terminals are identified.
2. Operational Tests: Schedule tests after
pre-testing has been successfully completed.
Test all modes of system operation and
intrusion detection at each detection
device. Test for detection of intrusion and
for false alarms in each protected zone.
Test for false alarms by simulating
activities outside indicated detection
patterns. Test for central station alarm
notification on all systems.
3. Electrical Tests: Comply with NFPA 72,
Section A-7. Minimum required tests are as
follows:
a. Verify the absence of unwanted voltages
between circuit conductors and ground.
b. Test all conductors for short circuits
using an insulation-testing device.
c. With each circuit pair, short circuit
at the far end of circuit and measure
circuit resistance with an ohmmeter.
Record circuit resistance of each
circuit on Record Drawings.
d. Verify that each control unit is in
normal condition as detailed in
manufacturer's operation and
maintenance manual.
e. One connection each should be opened at
not less than 10 percent of initiating
and indicating devices. Observe proper
signal transmission according to class
of wiring used.
f. Verify that transient surge-protection
devices are installed according to
manufacturer's written instructions.
Kommentare zu diesen Handbüchern