PI -- 34.65dProduct Information MAGIC.SENS -- Product r ange
Page 11 of 42
BDL--4998121218
A23.en /09.02.2007
ST--FIR/ PRM1 / deh
4.1. MAGIC.SENS OTC 410 LSN
O
eration locations that can be selected
Sensitivity
in the >WinPara< programming software
etector type
T
max
--unit O--unit C --unit
Theaters / Concert Halls combined
O+T
max
+T
diff
+C
high (A2) medium high
W arehouse with vehicle traffic combined
O+T
max
+T
diff
+C
low (B) low* low
Office (smokers) / Restaurant /
W aiting room / Conference room
combined
O+T
max
+T
diff
+C
high (A2) low* low
Conference room / Waiting room
/ Exhibition hall
combined
O+T
max
+T
diff
+C
high (A2) low* medium
Office (no traffic) combined
O+T
max
+T
diff
+C
high (A2) high high
School / Kindergarten combined
O+T
max
+T
diff
+C
high (A2) medium high
Garage combined
O+T
max
+T
diff
+C
high (A2) low* low
Kitchen / Casino /
Restaurant during active operation
combined
O+T
max
+C
low (B) low* low
Production Facilities combined
O+T
max
+T
diff
+C
low (B) low* medium
Computer room combined
O+T
max
+T
diff
+C
high (A2) high high
High--board warehouse without vehicle
traffic with combustion motors.
combined
O+T
max
+T
diff
+C
low (B) high high
Office (daily operation) combined
O+T
max
+T
diff
+C
low (B) medium high
*With low sensitivity of the optical sensor, the detector only triggers if smoke and also an increase of
the CO concentration or the temperature is detected.
4.2. MAGIC.SENS OC 410 LSN
O
eration locations that can be selected in the
Sensitivity
>WinPara< programming software
etector type
O--unit C--unit
Theaters / Concert Halls combined (O + C) medium
W arehouse with vehicle traffic combined (O + C) low
ally
n.
Office (smokers) / Waiting room / Restaurant / Conference
room
combined (O + C) low
ys equ
locatio
Conference room / Waiting room / Exhibition hall combined (O + C) low
lwa
ion l
Office (no traffic) combined (O + C) high
is
erat
School / Kindergarten combined (O + C) medium
unit
op
Garage combined (O + C) low
eC
fth
Kitchen / Casino / Restaurant during operation combined (O + C) low
of th
ss o
Production Facilities combined (O + C) low
ity
rdle
Computer room combined (O + C) high
siti
rega
High--board warehouse without vehicle traffic with
combustion motors
combined (O + C) high
he se
high, r
Office (daily operation) combined (O + C) medium
T