PI -- 34.65dProduct Information MAGIC.SENS -- Product range
Page6of42
BDL--4998121218
A23.en /09.02.2007
ST--FIR/ PRM1 / deh
2.3. System Description MAGIC.SENS ...LSN
Up to three detection principles are integrated into the multisensor detector
MAGIC.SENS . . . 400/410 LSN:
1. Optical (for smoke)
2. Thermal ( for heat) OTC, OC, OT, O, T
3. Chemical (for gas)
The individual sensors can be programmed via the LSN network manually or
time--controlled. All sensor signals are evaluated continually by the internal signal
analysis electronics and are linked with each other. By linking the sensors ( combined
detectors), the detector can also be used in places where the work carried out gives
rise to light smoke, steam or dust. If with the OC, OT, O, and T detectors a signal
combination fits the selected identifier for the area of operation, an alarm is triggered
automatically.
2.3.1.FeaturesMAGIC.SENS...LSN
D Active self--monitoring of the sensors, with display on the fire panel:
-- Display for defined sensor faults (life--zero monitoring),
-- Stepless display of the degree of contamination (only in service),
-- Fault indication with heavy contamination (instead of false alarm).
D Active adjustment of the threshold (drift compensation) if the optical sensor
becomes contaminated.
D Active adjustment of the threshold (drift compensation) of the chemical sensor.
D T he EMVsecurity is, with 30V/m in the range 1--1000MHz and with 40V/m in the
cellular frequency ranges 415--466MHz and 890--960MHz, significantly higher than
that required by VdS 2110 (VdS Schadenverhütung GmbH).
D Thanks to integrated isolators, the LSN ring will continue to function in case of
wire breakage or short--circuit of a detector.
D Detector individual identification on the fire panel in case of alarm. Alarm
display on the detector with a blinking red LED.
D Programmable, that is, can be adjusted to the area of operation.
D Increased detection and false alarm security thanks to evaluation of the temporal
behavior of fire and disturbance variables.
D Manual or time--controlled switch--off of individual sensors for adjustment to
extreme disturbance variables.
D Activation of a remote external detector alarm display is possible.
D Va riable mechanical removal safeguard (can be activated/deactivated).
D Dust--resistant labyrinth and cap construction.
D Can be connected to the LSN – fire panel BZ 500 / universal European central unit
UEZ 2000 / universal danger detection system UGM 2020 and to other central units
or their r eceiver components with identical connection conditions.
D Depending on the central unit, using the WinPara program (Version 4.53 or higher)
it is possible to read out the serial number, degree of contamination (for the O unit),
operating hours, and current analog values for each configured detector.