Bosch FPA-1200-MPC Betriebsanweisung Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 100
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
Notice!
A maximum of four fault messages can be displayed on the display at any time. Only fields
that can be operated are displayed (e.g. Acknowledge and Reset).
To display further fault messages, scroll down through the list. Refer to Scrolling through lists,
page 27 for information on how to scroll through a list.
The next four fault messages are displayed.
Sequence of the trouble messages
The messages are displayed in chronological order.
Notice!
15–30 seconds after the last entry (e.g. after scrolling through the list), the first and last fault
message is displayed at the beginning of the list again.
Information about malfunctioning element groups
The trouble message contains information about:
Element category
Message type
Address of the element group
Number of individual elements that have caused a fault in the respective element group
Message number
Additional information (e.g. the installation location)
Example:
Fault Zone 00005
#001 Office 1 (6)
Element category: Different detectors in one logical zone
Message type: Fault
Address of element groups 00005: The fifth logical zone caused the first fault.
Number of individual
elements
(6): In the fifth logical zone (00005), six detectors caused a
fault. For element groups that only consist of one element, the
number of elements is not displayed.
Message number The fault messages are numbered chronologically.
The message number in the second line indicates the sequence
in which the fault messages were received.
001: The first and oldest fault message received.
Installation location of the
logical zone
Office 1
Notice!
Depending on the configuration of the system, either the logical or physical address of the
element is displayed.
The newest message
The newest message is displayed at the end of the list.
11.2.2
11.2.3
11.2.4
Panel Controller Fault message | en 53
Bosch Sicherheitssysteme GmbH User Guide 2013.07 | 3.0 | F.01U.258.929
Seitenansicht 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 99 100

Kommentare zu diesen Handbüchern

Keine Kommentare