7-2 System Overview I-Remote
DOK-IWORKS-IREMOTE*V01-AW01-EN-P
I-Remote within a Local Network
If the service PC is in the same LAN as the control unit, then the remote
session can be run without any additional adjustment of the network. It is
thus irrelevant whether the service PC and the control unit are in different
subnetworks or not. In this case, the IP packages are routed between the
individual subnetworks.
If a former stand-alone control system group such as that shown below is
connected to the head station with the LAN, then appropriate adjustments
must be made to allow for communication between the service PC and
the group.
In the configuration shown, the head station is a multihomed system with
2 network interface cards. Even without use of a router, communication
between a control system group and the adjacent subnetwork can be
established within this configuration. IP forwarding must first be activated
at the head station. Then the head station must also be accepted into the
TCP/IP configuration as an additional gateway on the service PC and on
the control systems of the group. After this adjustment, the control system
groups can be remotely operated by the service PC.
TeleserviceLAN.JPG
Fig. 7-2: I-Remote within a local network