Bosch DS7400XiV4-EXP Spezifikationen Seite 112

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 144
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 111
DS7400XiV4-EXP | Reference Guide | 7. Reference Materials EN | 112
Bosch Security Systems | 1/05| 4998154963B
Entry/Exit Delay Cancel Zone Functions: Entry/Exit
Delay Cancel 1 and Entry/Exit Delay Cancel 2 Zone
Functions cause the exit delay to expire as soon as the
premises is vacated.
If a zone is programmed as an Entry/Exit Delay
Cancel zone, and it is activated during the exit
delay, the exit delay will expire as soon as the zone
has been restored.
Entry/Exit Delay Cancel 1 follows entry delay 1.
Entry/Exit Delay Cancel 2 follows entry delay 2.
Interior Entry/Exit Follower: This is a zone
programmed to be ignored during an entry/exit delay
and then become an interior instant zone.
If this zone is violated while the system is armed
and no entry/exit zones have been violated, it will
activate an alarm.
If this zone is violated after an entry/exit delay
zone is violated, it will follow that entry/exit delay
time.
This zone is bypassed by Perimeter Instant or
Perimeter arming.
Interior Home/Away: This is a zone programmed to
become an interior instant zone if the system is armed
and an entry/exit delay zone is violated during the exit
delay time.
If the system is armed and an entry/exit delay zone
is not violated, this zone will be bypassed.
This zone is bypassed by Perimeter Instant or
Perimeter arming.
Interior Instant: This is a zone programmed to activate
an alarm even during the entry/exit delay periods.
It is bypassed by Perimeter Instant or Perimeter
arming.
Day Monitor: This is a zone programmed to be a
perimeter instant zone when the system is armed.
When the system is disarmed, any violation of this
zone will activate the keypad sounders which will
sound continuously until a disarm command
sequence is entered.
The alarm outputs for this zone will not activate
and there will be no report for this zone when the
system is disarmed.
Keyswitch Input: This is a zone programmed to allow
the system to be armed or disarmed using a Normally
Open momentary keyswitch.
Outputs for keyswitch LEDs and sounders are
available using the programmable outputs or the
Octal relay outputs.
An output is needed for each LED and sounder.
A keyswitch will only control the area that these
zones are assigned to unless programmed as a
master, then it will control all at once. See
Program Address 0001, Data Digit 1.
Keyswitches and keypads may be used in the same
area, if desired.
Fire Zone: This is a zone programmed to activate if
the system is armed or disarmed.
It can be silenced (not reset) by entering a valid
[PIN][Off].
The display will indicate a Fire Alarm for this zone
on all keypads in every area.
A fire reset command must be entered after
silencing the alarm to re-enable this zone.
If this zone is programmed for trouble and the
loop opens, the DS7447E/DS7447V2 keypad will
display "Fire Trouble" for this zone and the
keypad sounders will beep once every ten
seconds.
If the system is a combination fire and burglar
alarm, the fire alarm has priority over the burglar
alarm.
Fire Zone with Verification: This zone is identical to
a Fire Zone except that after the first alarm, it will
perform a fire reset and then wait up to two minutes
for a second alarm.
If a second alarm occurs within this two minute
period, the system will indicate a fire alarm.
If there is no second alarm within this two minute
period, the control panel will reset back to its
normal condition.
Seitenansicht 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 143 144

Kommentare zu diesen Handbüchern

Keine Kommentare