DS7400XiV4-EXP | Reference Guide | 7. Reference Materials EN | 116
Bosch Security Systems | 1/05| 4998154963B
Special Emergency Key: The emergency key (key B)
at the bottom center of the keypad entry area is the
Special Emergency Key.
If programmed, the key will activate a
supplementary or an auxiliary type alarm when
pressed for 2 seconds.
It may be programmed for a silent, steady, or
pulsed alarm.
Panic Key: The emergency key (key C) at the bottom
right of the keypad entry area is the Panic Key.
If programmed, the key will activate a panic alarm
when pressed for 2 seconds; nothing will display at
the keypad to indicate an alarm.
It may be programmed for a silent, steady, or
pulsed alarm.
The Special Emergency Key and the Panic
Key will generate the alarm sounders only
in the area of the keypad that activated that
Key.
7.2.8 Custom Arming Programming
Custom Arming - [PIN ][#][4]: If programmed, the
[PIN][#][4] command sequence may be used to custom
arm the system by arming only certain zone functions.
For example: All interior zones plus some
perimeter zones may be bypassed while leaving
some of the perimeter armed.
7.2.9 Force Arming
Force Arming: If programmed, allows violated zones
to be force armed. When force arming, the user must
enter the usual arming command followed by the
[Bypass] key. This automatically bypasses zones that are
violated and programmed as bypassable.
Fire zones, supervisory zones, keyswitch zones,
waterflow zones, and non-bypassable zones can not
be force armed.
See Section 5.9.14 Force Arming and Ground Fault
Detect Programming for more information.
7.2.10 Ground Fault Detect Programming
Ground Fault: If programmed, this function will
allow the system to detect ground faults. This
function is required for fire panels and will be
forced on when the control panel is in the
commercial fire mode.
See Section 5.9.14 Force Arming and Ground Fault
Detect Programming for more information.
7.2.11 Commercial Fire Mode Programming
In a system that includes both fire alarm
and burglar alarm devices, the system must
produce distinct sounds for fire and burglar
alarm conditions either by using different
indicating appliances or by using distinct
cadences for the same appliance.
Commercial Fire Mode: When in Commercial Fire
Mode, the control panel will perform some functions
(for example, communications) differently to conform
with commercial fire regulations.
See Section 5.9.15 Commercial Fire Mode
Programming for more information.
Water Flow Zone Delay: This is the amount of time
a water flow zone must be violated before the control
panel will initiate an alarm.
The delay is necessary to accommodate normal
changes in water pressure.
If the water flow initiating device incorporates its
own time delay, do not program the control panel
unit to exceed 120 seconds combined time delay.
Pulsing Fire Zone: This is a zone programmed to
output a pulse for a fire alarm in the normal manner
(one second ON, one second OFF).
California March Time: This is a zone programmed
to output a pulse for a fire alarm in the California
Time cadence (ten 1/2 second pulses, followed by one
second of quiet time).
Temporal: This is a zone programmed to output a
pulse for a fire alarm in the Temporal cadence (three
1/2 second pulses, followed by one second of quiet
time).
Single Keypad Use: The keypad should be used on
the keypad bus and be mounted to the front of the
control panel enclosure OR if within the same room as
the control panel equipment with the wire run in
conduit (or equivalently protected against mechanical
injury) within 20 ft. (6.1 m) of the control panel
equipment.
This keypad should be assigned as address 1.
Multiple Keypad Use: One keypad only must be used
on the option bus, at any address from 11 to 14, and
must meet the following requirements:
The keypad must be mounted to the front of the
control panel enclosure OR mounted within the
same room as the control panel equipment and the
wire is run in conduit (or equivalently protected
against mechanical injury) within 20 ft. (6.1 m) of
the control panel equipment.