DS7400XiV4-EXP | Reference Guide | 5.0 Programming the Control Panel EN | 75
Bosch Security Systems | 1/05| 4998154963B
Table 104: Octal Relay Address B Selections
Selections for
Data Digits 1 & 2
Follow Action Select Options DD1 DD2
Latch ON after Zone Alarm
1
0 0
ON during Entry Pre-Alert 0 1
ON for 10 sec after pressing
[System Reset]
0 2
ON for Any Armed state 0 3
Ground Start 0 4
System Status (Ready to Arm) 0 5
Zone Alarm 0 6
Zone Alarm Delayed by 20 sec 0 7
Keypad Sounder Output 0 8
Access Output (10 sec pulse) 0 9
Future Selection 0 *0
Panic/Duress Output
2
0 *1
ON when System is Partial 0 *2
ON when System is Fully Armed 0 *3
1
This includes invisible zones. See the glossary for details.
2
See Section 7.2.4 Output Programming for a description of
this option.
Follow System Wide Event (Addresses 2740 to
(2771)
• Program Address A: 2740 to 2770
• Data Digit:
• Data Digit 1:
2 (default = 1)
• Data Digit 2: ____ (default = 3)
• Program Address B: 2741 to 2771
• Data Digit:
• Data Digit 1: ____ (default = 0)
• Data Digit 2: ____ (default = 6)
To program an Octal Relay Module for Follow System
Wide Event:
1. Select the Octal Relay to program (see Table 105).
2. Program Data Digit 1 of Program Address A as 2
for Follow System Wide Event.
3. Program Data Digit 2 of Program Address A for
the desired function (see Table 106).
4. Program Data Digit 1 and 2 of Program Address B
for the desired function (see Table 107).
5. Once both Address A and Address B have been
programmed, proceed to program the next Octal
Relay.
For Octal Relay Partition Assignment, see Octal Relay
Module Output Partition Assignment (Addresses 2844 to
2851) on page 80.
Table 105: Octal Relay Program Addresses
DX3010-1 Octal Relay
Number
Address A
(see Table 106)
Address B
(see Table 107)
1 2740
2
2741
2 2742
2
2743
3 2744
2
2745
4 2746
2
2747
5 2748
2
2749
6 2750
2
2751
7 2752
2
2753
8 2754
2
2755
9 2756
2
2757
10 2758
2
2759
11 2760
2
2761
12 2762
2
2763
13 2764
2
2765
14 2766
2
2767
15 2768
2
2769
16 2770
2
2771
Table 106: Octal Relay Address A Selections
Selections for
Data Digit 2
Follow System Wide Event
Select Options
0 1 2 3