Example : Data Bus Location 103 - DIP Settings
On
Off
Figure 5.5: DX2010 DIP Switch Settings
Status Indicator
Flashing once per second: Indicating normal operation.
Constant illumination indicates following conditions:
The grounding conductor is not connected or there is communication failure between the
alarm control panel and the module.
No zones are distributed to modules with corresponding addresses.
Module address setting error.
Off: The module is de-Energized.
DIP Switch
Status Indicator
Figure 5.6: DX2010 Status Indicators
Test
The alarm control panel tests the communication normally with the module. In case of
communication failure, a fault report with the module address is sent.
5.2.5
5.2.6