Loop resistance (ohm) Zone Status
Min Type Max
o 1430 tamper
1650 2200 2750 normal
2970 4400 4950 triggered
5220 tamper
Using one 2.2K resistor as EOL of the tamper zone, which works together with the zone EOL
2.2K. Refer to the drawing:
COM
Z3
BBBBB7DPSHU6ZLWFK
BBBBB=RQH6ZLWFK
1
2
On -board Tamper Input
A separate input is provided for enclosure tamper (This is in addition to the 8 on-board total
inputs). The response time of the tamper input is a fixed zone response time. The tamper loop
will cause a siren alarm when the loop is open, and will be reported when the loop is open
(based the “system status report option”).When powered up, the system will wait for 60
seconds to setup the normal work.
Tamper Switch connector Input:
Close: Normal
Open: Alarm Tamper Alarm process is the same as 24-Hour Alarm process (Onboard Tamper is
processed as zone number 17).
Zone Function Settings / Zone Types
Zone Types
Zone Function Option Description
Zone Type 00 Zone Not Used
01 Instant
02 Interior Instant
03 Delay
04 Interior Delay