Programmable Outputs
The control panel has four fully programmable outputs on the main printed circuit board and
one programmable output that operates the codepad buzzer. The four outputs are set by
default to operate as an alarm device, fire alarm verification, strobe, and internal screamer.
Programmable outputs require four parameters to operate correctly.
Parameter Description
Event Type The Event Type specifies when an output is activated. Enter the
code for the Output Event Type into the two corresponding
locations for the output.
Polarity Polarity determines whether the output operates for the duration
of the event, pulses for the duration, operates only once (one
shot), or latches on.
Time Base/Time
Multiplier
The Time Base and Time Multiplier parameters determine how
long and how often the output operates.
Table 15.1: Output Parameters
Output Programming
Item Location Default New Item Location Default New
Output 1 (Default = Horn Speaker) Relay Output (Default = Sirens Running)
Event Code 0436 1 Event Code 0454 1
Event Code 0437 14 Event Code 0455 15
Polarity 0438 0 Polarity 0456 1
Time Base 0439 0 Time Base 0457 0
Time Base Multiplier 0440 0 Time Base Multiplier 0458 0
Time Base Multiplier 0441 0 Time Base Multiplier 0459 0
Output 2
(Default = Fire Alarm With Verification)
Codepad Buzzer
(Default = Entry/Exit Warning and Day Alarm)
Event Code 0442 2 Event Code 0460 0
Event Code 0443 7 Event Code 0461 13
Polarity 0444 10 Polarity 0462 2
Time Base 0445 2 Time Base 0463 1
Time Base Multiplier 0446 1 Time Base Multiplier 0464 0
Time Base Multiplier 0447 5 Time Base Multiplier 0465 1
Output 3 (Default = Strobe – Reset After 8 hrs.)
Event Code 0448 2
Event Code 0449 0
Polarity 0450 6
15
15.1
128 en | Programmable Outputs Control Panel
2014.07 | 00n | F01U298026 Installation Guide