2. Press [7][2][1] to access the Network Module menu.
3. Set both modules to 2 – Used, Config.
4. Continue to press [-] until you return to Confirm to Save Parameter Changes.
5. Press [#] to save the changes.
6. Power off the control panel, then power it back on.
7. Press [7][2][1] to return to the Network Module menu.
8. Set both modules to 1 – Used, Not Config.
9. Continue to press [-] until you return to Confirm to Save Parameter Changes.
10. Press [#] to save the changes.
B426 Conettix Ethernet Communication Modules
The B426 Conettix Ethernet Communication Module is a four-wire powered SDI, SDI2, or
Option bus device that provides two-way communication with compatible control panels over
IPv4 or IPv6 Ethernet networks.
Typical applications include:
Reporting and path supervision to a Conettix Communications Receiver/Gateway.
Remote administration and control with A-Link Plus or our Remote Security Control
application for handheld devices.
Connection to building automation and integration applications.
The B426 is built for a wide variety of secure commercial and industrial applications. Flexible
end-to-end path supervision, AES encryption, and anti-substitution features make B426
desirable for high security and fire monitoring applications. It is capable as a stand-alone path
or it can be used in conjunction with another communication technology. For Fire Monitoring
applications, the B426 meets UL864 and NFPA72 standards for Single Communication
Technology with approved Bosch control panels.
B450 Conettix Plug-in Communicator Interfaces
The B450 Conettix Plug-in Communicator Interface is a four-wire powered SDI2, SDI, or option
bus device that provides two-way communication with compatible control panels over
commercial cellular networks using a plug-in communicator (available separately).
Use the B450 in combination with a plug-in communicator for primary or backup alarm
communication, remote control panel programming and other remote applications. The B450
supports Conettix IP protocol with full authentication, 256 bit AES encryption and resistance
to Denial of Service attacks. Use the B450 to add cellular network communications to existing
or new commercial security and fire installations.
Switch addressing
Use the address switch to assign a bus address or setup for USB or SMS configuration where
required. The address switch allows bus address selection.
Configuration
For most installations, the default B450 settings allow installation with no device programming
required. For customized network settings, the B450 supports a USB configuration menu, or
configuration via SMS.
When the B450 is running in version 3 compatibility mode, it reports its module type as a
B426. Networking parameters can be configured using A-Link. When the cellular specific
parameters need to be modified, use USB or SMS to configure the module directly.
When the B450 is running in version 4 compatibility mode, it reports its own product type.
Both networking parameters and cellular specific parameters can be configured using A-Link.
4.10
4.11
38 en | Accessories Control Panel
2014.07 | 00n | F01U298026 Installation Guide