6-16 Order data/reference lists Rexroth SYNAX 200
DOK-SYNAX*-SY*-12VRS**-PR01-EN-P
Input module RME02.2-16-AC115
SG100024V01_NN.bmp
Fig. 6-32: RME02.2-16-AC115
AC sources of a maximum rating of 120VAC / 60Hz can directly be
connected to the digital 115VAC input modules. The 16 AC inputs are
arranged in 2 isolated potential groups.
A detailed description can be found in documentation "SERCOS I/O Unit
RECO02.2 - Project Planning Manual" (DOK-CONTRL-RECO02.2***-
PRJ1-EN-P).
1
2
3
4
5
6
7
8
9
10
R
ME02.2-16-AC115
COM
COM
GND
Z
E
I*.0.0
I*.0.1
I*.0.2
I*.0.3
I*.0.4
I*.0.5
I*.0.6
I*.0.7
I*.1.1
I*.1.2
I*.1.3
I*.1.4
I*.1.5
I*.1.6
I*.1.7
I*.1.0
Specifications:
- Low: < 35V AC
- High: 85 ... 138V AC
- Input current I
E
High < 15mA
- Power loss Pv ca. 3W
- Weight ca. 300g
115VAC
NL1
SF100003V01_EN.FH7
X1 X2
Fig. 6-33: General specifications and pin assignments RME02.2-16-AC115
Brief description
RME02.2-16-AC115
Documentation
RME02.2-16-AC115
General specifications
RME02.2-16-AC115