8-4 Set-Up interfaces (SynTop, DOLFI) Rexroth SYNAX 200
DOK-SYNAX*-SY*-12VRS**-PR01-EN-P
Cable from the PC to the converter
The cable from the PC to the interface module is constructed as follows:
3
2
4
9-pin, bushing
TxD
RxD
DTR
RS232 cable from PC to converter
YF000211V01_EN.FH7
8
7
CTS
RTS
5
GND
6DSR
PSM-EG.: D-subminiature
3
2
4
TxD
RxD
DTR
8
7
CTS
RTS
5
GND
6DSR
9-pin, bushing
PC side: D-subminiature
connector
housing
connector
housing
Fig. 8-6: Cable from PC to converter (valid for PSM-EG-RS232/RS485-P/2D
and PSM-ME-RS232/RS485-P)
Note: The connection from pin 3 to pin 7 at the side of the converter
at the PSM-ME-RS232/RS485-P is not necessary. If you use
mixed service between PSM-EG-RS232/RS485-P/2D and
PSM-ME-RS232/RS485P the connection from pin 3 to pin 7
should be installed because otherwise it's only possible to get
a communication between PC and PSM-ME-RS232/RS485-P
converter.
3
2
4
9-pin, bushing
TxD
RxD
DTR
RS232 cable from PC to converter
YF000212V01_EN.FH7
8
7
CTS
RTS
5
GND
6DSR
PSM-ME: D-subminiature
3
2
4
TxD
RxD
DTR
8
7
CTS
RTS
5
GND
6DSR
9-pin, bushing
PC side: D-subminiature
connector
housing
connector
housing
Fig. 8-7: Cable from PC to converter (only valid for PSM-ME-RS232/RS485-P)
Cable valid for
PSM-EG and PSM-ME
Cable only valid for PSM-ME