Rexroth SYNAX 200 Fibre-optics cable connections 7-7
DOK-SYNAX*-SY*-12VRS**-PR01-EN-P
Handling
Connecting the fibre-optics cables
Fibre-optics cables are connected as follows at the transmitter
TX (PPC-R, PPC-P)
X10 (DSS 2.1 in Diax 03 or Diax 04 and EcoDrive)
X20 (IndraDrive, EcoDrive 03, EcoDrive Cs).
Fibre-optics cables are connected as follows at the receiver
RX (PPC-R, PPC-P)
X11 (DSS 2.1 in Diax 03 or Diax 04 and EcoDrive)
X21 (IndraDrive, EcoDrive 03, EcoDrive Cs).
Storage
When storing the fibre-optics cables, please note that
• the protective caps must be in place
• the mechanical limit values are maintained
• the thermal limit values are maintained.
Routing and mounting
When routing and mounting the fibre-optics cables, please note that the
specific load data do not damage the fibre-optics cables.
The minimum bend radius may not be exceeded (e.g., when routing
around corners).
The maximum cross stress may not be exceeded (e.g., when routing
around corners). In cable channels, please note that the fibre-optics cable
is not subjected to excessive cross stress. This can be caused for exam-
ple by the weight of power cables.
Routing over sharp edges or pointy, uneven surfaces must be avoided.
Any cuts or mechanical damage could cause interference.
Avoid twisting the fibre-optics cable when routing. There may be no ten-
sion in the final position of the fibre-optics cable.
Connections transmitter side
Connections receiver side
Bend radius
Cross stress
Do not twist fibre-optics cable