ECODRIVE Drive Controller DKC02.1
DOK-ECODRV-SSE-03VRS**-WAR1-EN-P • 12.96 Error Diagnostic Messages 2-9
F401 Double MST Error Shutdown
The drive has not received the master synchronization message frame in
two consecutive SERCOS cycles.
Cause:
1. Malfunction in the fiber optics cable
2. Excessive damping of the light signals
3. (General) malfunction in the SERCOS interface
4. Master failed
Remedial action:
Ref. 1. Check all fiber optics connections in the SERCOS loop.
Ref. 2. Measure the damping in the fiber optics cables.
The maximum damping between TX and RX may not fall
below 12,5 dB.
Ref. 3. Replace the SERCOS interface module in the drive.
Ref. 4. Check the master if all slaves have stopped.
F402 Double MDT Error Shutdown
The drive has not received the master data message frame (MDT) in two
consecutive SERCOS cycles.
Cause:
1. Malfunction in the fiber optics cable
2. Excessive damping of the light signals
3. (General) malfunction in the SERCOS interface
4. Failure of the complete bus
Remedial action:
Ref. 1. Check all fiber optics connections in the SERCOS loop
Ref. 2. Measure the damping in the fiber optics cables.
The maximum damping between TX and RX may not fall
below 12,5 dB.
Ref. 3. Replace the SERCOS interface module in the drive
Ref. 4. Check the master
F403 Invalid Communication Phase Shutdown
The SERCOS master module has specified an illegal communication
phase (phase > 4).
Cause: Error in the controller’s SERCOS master module.
Remedial action: Contact the controller manufacturer.