ECODRIVE Drive Controller DKC02.1
DOK-ECODRV-SSE-03VRS**-WAR1-EN-P 12.96 Warning Diagnostic Messages 3-5
E829 Positive Position Limit Value Exceeded
The drive has received a command value that has led to an axis position
outside the positive travel range. The axis is stopped by setting the
velocity command value to zero. A class 1 diagnostics error is not
generated. The drive automatically follows command values that lead
back to the valid range. Bit 2 of S-0-0090, Command Value Transmit
Time (TMTSG) has been set to "Exceeding the travel limit is considered
as a warning".
Cause:
S-0-0049, Positive position limit value exceeded.
Remedial action:
Specify command values that lead back to the valid range.
E830 Negative Position Limit Value Exceeded
The drive has received a command value that has led to an axis position
outside the negative travel range. The axis is stopped by setting the
velocity command value to zero. A class 1 diagnostics error is not
generated. The drive automatically follows command values that lead
back to the valid range. Bit 2 of S-0-0090, Command Value Transmit
Time (TMTSG) has been set to "Exceeding the travel limit is considered
as a warning".
Cause:
S-0-0050, Negative position limit value exceeded.
Remedial action:
Specify command values that lead back to the valid range.
E843 Positive Travel Zone Limit Switch Activated
The drive has received a command value that has led to an axis position
outside the positive travel range. The axis is stopped by setting the
velocity command value to zero. A class 1 diagnostics error is not
generated. The drive automatically follows command values that lead
back to the valid range. Bit 2 of S-0-0090, Command Value Transmit
Time (TMTSG) has been set to "Exceeding the travel limit is considered
as a warning".
Cause:
The positive travel zone limit switch has been actuated.
Remedial action:
Specify command values that lead back to the valid range.