ECODRIVE Drive Controller DKC02.1
DOK-ECODRV-SSE-03VRS**-WAR1-EN-P 12.96 Command Diagnostic Messages 4-13
C604 Homing of absolute encoder not possible
The command S-0-0148, C6 Drive controlled homing procedure has
been started. The encoder selection in S-0-0147, Homing Parameter
has selected an absolute measuring system. The command can only be
executed if the command P-0-0012, Command ’Set Absolute
Measurement’ has been activated beforehand.
Remedial action:
Execute the command P-0-0012, Command ’Set Absolute
Measurement before you start the command S-0-0148, C6 Drive
controlled homing procedure. This action establishes the absolute
dimension reference.
C605, Homing velocity too great
Cause:
Unequivocal allocation of a reference marker to a zero switch is not
possible at a high velocity since the zero switch is only evaluated every
2 ms.
Remedial action:
Reduce the value of S-0-0041, Homing velocity.
C700 Basic load
With motors of the MDD and MKD series, the mechanical system of the
machine is adapted to the digital drive by activating the speed controller
parameters that are stored in the motor feedback. The drive controller
employs the C7 message to indicate that the command C700 initial
program loading has been activated via the command S-0-0262,
Command Basic Load.
Cause:
The command C700 initial program loading has been activated.
C800 Command Base-Parameter load
Description:
Pressing the S1 button on the drive controller when the display shows
"PL" or starting P-0-4094, Command Parameter Default Set clears all
parameters and sets them to a default value that is stored in the
software.
The motion blocks will be lost, too.