Buzz on Fail
Default: No
Selection:
Yes or No
Yes Generate panel-wide trouble tones and
display PHONE FAIL # at keypads
when a Phone Fail Event occurs.
No Does not generate trouble tones at
keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
Phone Supv Time must be programmed to
use this feature.
When
Buzz on Fail
is Yes, users can disable the
resulting trouble tone on individual keypads by setting
CC# Trouble Tone
to No.
Two Phone Lines
The D7212GV2 does not support the use
of the D928 Dual Phone Line Switcher.
Leave this prompt set to its default value.
BFSK Duress Code
Default: 0
Selection:
0 to 9
If
Duress Enable
in Area Parameters is Yes and
Modem Format
in Phone Parameters is No, you must
program a number to identify Duress Reports at the
central station.
Expand Test Rpt
Default: No
Selection:
Yes or No
Yes Off-normal events listed in Routing
Group Test Reports are reported to
the central station.
No Off-normal conditions for the events
listed in the Routing Group Test
Reports at test time are not reported.
Use this program item to add system event
information to scheduled Test Reports. Refer to Section
5.2 Skeds on page 107.
This parameter relates to Sked Function
Code 9 (Test Report) because it allows a
Sked to send Expanded Test Report
information. Expand Test Rpt does not
affect Sked Function Codes 28 (Expanded
Off-Normal Test Report) and 29 (Non-
Expanded Off-Normal Test Report).
2.3 Routing
Use routing to select full or partial groups of events
that report to up to four different destinations. Routing
includes choosing the most important destination
(route number), reporting the events to a single or
multiple destination, and selecting a backup
destination if the events fail.
2.3.1 Called Party Disconnect
Telephone companies provide called party disconnect
to allow the called party to terminate a call. The called
party must go on hook (hang up) for a fixed interval
before a dial tone is available for a new call. This
interval varies with telephone company equipment.
D7212GV2 firmware allows for called party
disconnect by adding a 35-sec on-hook interval to the
dial-tone detect function. If the control panel does not
detect a dial tone in seven sec, it puts the phone line
on hook for 35 sec to activate called party disconnect.
The phone line goes off hook and begins a seven-sec
dial tone detect. If no dial tone is detected, the control
panel dials the number anyway. Each time the number
is dialed, the control panel records this as an attempt.
After ten attempts, the control panel enters
communications failure and Comm Fail Route #
appears on the keypads.