D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 27
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
2.6 Printer Parameters
One D9131A Parallel Printer Interface Modules can
be connected to the SDI bus in the D7212GV2. The
printer is identified by an address of 17. Options are
available for Routing Reports and area assignments.
Printer Address
Default: 17
Selection:
17
Enter the printer address you are programming.
P## Area Assign
Default: 1
Selection:
1 to 4
Assign an area to the printer programmed in
Printer
Address
.
P## Supervised
Default: No
Selection:
Yes or No
Yes Only one printer can be installed for
this
P## SDI
address.
No More than one unsupervised printer
can be installed using this
P## SDI
address and the same address DIP
switch setting.
Supervise this SDI address. Generate Trouble SDI ##
Reports and local trouble annunciation if a problem
occurs with this printer or the SDI bus.
Unsupervised printers sharing the same
address setting print the same text.
Trouble SDI ## Reports are always
reported as Area 1, Account 1 Events
regardless of where the SDI device is
assigned.
When P## Supervised is set to Yes and
all Printer Event Groups (such as P## Fire
Events, P## Burglar Event, or P## Usr
Chng Evt) are set to No, the control panel
does not generate Trouble SDI ## Reports
for the printer if the D9131A becomes
disconnected.
P## Scope
Default: No Printer
Selection:
No Printer, Area, Account, Panel
Wide, Custom
Panel
Wide
Printer prints all designated events that
occur panel-wide. A panel-wide printer
can cross account boundaries.
Account Printer prints all designated events that
occur within any area with the same
account number in which this printer
is assigned.
Area Printer prints all designated events that
occur in the area to which this printer
is assigned.
Custom Printer prints all events occurring in
areas programmed Yes for this prompt
regardless of any boundary restrictions.
No Printer No printer installed at this address. If a
printer is connected, data does not
print.
Press the [SPACE] bar to scroll through the selections.
Press [ENTER] when the correct selection appears in
the display.
The following prompts are visible only
when you program P## Scope to Custom.
P## A1 [through A4] in Scope
Default: No
Selection:
Yes or No
Yes Include Area # Events in the scope of
this printer.
No Does not include Area # Events in the
scope of this printer.
Only available if
P## Scope
is programmed Custom.
This program item determines if events occurring in an
area print at this printer.
Refer to the report tables in Section 2.3
Routing on page 12 to identify the events
that print. Events programmed as No in
Routing still print at the local printer.
Individual events within the report group
cannot be suppressed for events printed at
the local printer.
Kommentare zu diesen Handbüchern