D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 57
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
Watch Mode
Default: E
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
6 Watch Mode [COMMAND][6]
This function informs you when a perimeter point or
interior point that is programmed as
P## Watch
Point
is faulted while the area is disarmed. Interior
points do not emit a Watch Tone if the area is
perimeter armed. This function provides keypad
audible or visual and optional relay activation (refer to
A # Watch Mode
in Section 2.13.1 Area Relays on page
71).
Perim Partial
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
7 Perimeter Partial
Arm
[COMMAND][8]
Use this function to arm normal perimeter points and
force-bypass faulted perimeter points, regardless of
their P## Bypassable setting. When these force-
bypassed perimeter points return to normal, they
automatically return to service, even if P## FA
Returnable is set to No.
Perimeter Partial arming has entry and exit delays.
Perim Partial ignores the A# FA Bypass
Max entry in Section 2.9 Area Parameters
on page 31.
Local Only Reporting: No Closing Report
is sent to the central station, but a
Perimeter Delay Closing Event is generated
in the event log.
View Area Stat
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
8 View Area Status (Menu function only)
Use this function to view the armed status of all areas
within the scope of the keypad assigned to this area.
The armed states include A# AREA # IS OFF
(disarmed), A# AREA # IS ON (master delay armed),
ALL ON INSTANT (master instant armed), and
AREA # PERIM ON (perimeter instant armed or
perimeter delay armed). All area types, master,
associate, regular, and shared can be viewed using this
function.
View Memory
Default: E
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
9 View Event
Memory
[COMMAND][4][0]
Use this function to view prior alarm, trouble, and
supervisory activity occurring since the last time the
system armed. Event memory is not cleared until the
area re-arms.
View Pt Status
Default: E
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
10 View Point Status (Menu function only)
Use this function to view points assigned to the area
where the keypad is assigned. This function shows
point text and the electrical condition (normal, open,
short, and missing) of each point in the area.
Walk Test
Default: E
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
11 Walk Test [COMMAND][4][4]
Use this function to test Controlled points in areas
within the keypad’s scope without sending reports to
the central station. 24-hour points cannot be tested
using this Walk Test Mode.