
D7212GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 93
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
You should dedicate a fire annunciation
device to all your Fire points if they are
assigned to a single area in a multiple area
system. Special red keypads and
annunciators with specific keys for fire
systems are designed for this type of
application (D1256RB and D1257RB).
Do not use the Cross point function for Fire
points.
P## Alarm Verify
Default: Refer to the program record sheet
Selection: Yes or No
Yes Enable alarm verification on this point.
Alarm verification points must be
programmed as resettable.
No
Disable alarm verification on this
point.
Use this option only with Fire points to designate them
for alarm verification.
When an Alarm Verification point enters into alarm,
the control panel removes power to all Resettable
points for the duration programmed in
A# Verify
Time
in Section 2.9 Area Parameters on page 31. If the
point (or another Resettable point in the area) is still
faulted, or returns to a faulted state within 60 sec after
the initial verification time reset, an alarm is generated.
During a Fire Walk Test, the reset time is 5
sec. The time programmed in A# Verify
Time is ignored.
P## Resettable
Default: Refer to the program record sheet
Selection: Yes or No
Yes
This point is reset by the Reset Sensor?
function and during the alarm
verification sequence.
No This point is not resettable.
Use this option if this is a Powered point that requires
interruption of power to reset a latched alarm
condition. The Resettable point option is typically used
with smoke detectors and glass break detectors.
When initiated (either through a Fire Walk Test or the
keypad’s Reset Sensor? function) or when the remote
programming software (RPS) interrupts power to the
device for 5 sec, a Sensor Reset report is sent to the
central station receiver.
When a sensor reset occurs, the control
panel does not accept alarms from any
points with P## Resettable programmed
as Yes. During the 5-sec reset time, alarms
from these points are ignored.
Do not mix fire and intrusion devices on the
same powered loop.
P## Alarm Abort
Default: Yes
Selection:
Yes or No
Yes If the point goes into an alarm
condition, the system delays the alarm
report for the amount of time specified
in the control panel-wide parameter
Abort Window
.
No If the point goes into an alarm
condition, alarm reports are sent
immediately.
This parameter allows points with the associated Point
Index to delay a Burglar Alarm (non-fire) event for the
time period specified in the Abort Window. An alarm
is aborted by performing an alarm silence operation at
a keypad showing the burglar alarm condition before
this time elapses.
When an alarm is successfully aborted, the keypad
shows an optional ALARM NOT SENT message and no
event is sent or written in the control panel event log.
Refer to
CC# Abort Display
on page 51.
For SIA CP-01 Compliance:
P## Alarm Abort
can be set to Yes or No.
This feature does not apply to Fire Alarms
or invisible point alarms.
Kommentare zu diesen Handbüchern