MPH-02, MPB-02, MPD-02 Extended Drive Functions 9-3
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note: The rapid digital inputs have to be assigned to the parameters
S-0-0401 and S-0-0402 (default setting of P-0-0300, Digital
I/Os, assignment list etc.)!
See "Digital Inputs/Outputs" in the same chapter
A switching edge at the probe input can trigger the detection of a
measured value. Switching edges, however, only cause a measured
value to be detected when the following requirements have been fulfilled:
The presetting for measured value detection with positive and/or
negative switching edge at the respective probe input was activated in
S-0-0169, Probe control parameter.
The measured value detection was started via S-0-0170, Probing
cycle procedure command.
The respective probe input for measured value detection was enabled
(S-0-0405, Probe 1 enable or S-0-0405, Probe 2 enable).
DK0001v1.fh7
detecting the selected
signal at this point of time
in "probe value positive";
generating new
probe value difference
"probing cycle procedure" command
t (in ms)
probe enable
probe negative latched
detecting the selected
signal at this point of time
in "probe value negative";
generating new
probe value difference
probe
probe positive latched
Fig. 9-1: Evaluating the probe signal edges (with evaluation of positive and
negative edges in S-0-0169 switched on)
In parameter S-0-0169, Probe control parameter it is possible to set,
separately for probe 1 and 2, in which mode the measurement is to take
place. The measured value detection must have been activated.
The following enable modes are possible:
Single measurement
After the respective probe has been enabled (S-0-0405 or S-0-0406) a
value is only detected at the first measured value trigger. Before every
other measurement a repeated probe enable is required!
Continuous measurement
After the respective probe has been enabled (S-0-0405 or S-0-0406) a
new measured value is detected at each measured value trigger.
Activating the Measured Value
Detection
Mode of Measured Value
Detection